Coal analysis can be reported to a range of different "basis" depending on the purpose of the analysis. For example, "as received" or "as sampled" basis is used to understand the concentration of analytes in a coal including all the surface moisture. In contrast, reporting results on a "dry, ash-free" basis can be useful to understanding the rank of the coal, particularly when reviewing Volatile Matter, Hydrogen or Carbon concentrations. There may also be commercial reasons why a particular moisture basis is required, notably when a coal contract is written to a specified moisture basis, for example "2.5% moisture" basis
When the basis changes the associated analytical results will also change. Consequently, when comparing results it is important to compare them on the same basis.
There are a range of commonly used coal bases, each of which has a prescribed abbreviation. Bases include:
The relationship between the various bases is provided in the figure below.

The general equation for conversion from one moisture basis to another moisture basis is as follows:
General Equation:
100 – moisture basis required . analyte result as analyzed = analyte at required moisture basis
100 – moisture basis as analyzed
Example 1: You have a set of air-dried results where the as-analyzed Moisture is 2.0% (ad) and Ash is 12.0% (ad). For a contract you are required to report the Ash to a Moisture basis of 3.0% basis.
100 – Moisture (required basis) . Ash result (ad) = Ash result (at required basis)
100 – Moisture (ad)
(100 – 3.0) . 12.0 = 11.9% (ad)
(100 – 2.0)
Example 2: You are required to report an Ash value to Total Moisture (ar) basis where the air dried Moisture is 2.0% (ad), the air dried Ash is 12.0% (ad) and the Total Moisture is 10% (ar).
100 – Moisture (ar) . Ash result (ad) = Ash (ar)
100 – Moisture (ad)
(100 – 10.0) . 12.0 = 11.0% (ar)
(100 – 2.0)
Example 3: You analyzed a sample which has the following characteristics: Moisture 2.0% (ad), Ash 12.0% (ad) and Volatile Matter 29.5% (ad). You are required to calculate the Volatile Matter to a dry, ash free (daf) basis.
100 – Moisture (daf) + Ash (daf) . Volatile Matter (ad) = Volatile Matter (daf)
100 – Moisture (ad) + Ash (ad)
(100 – (0 + 0)) . 29.5 = 34.3 (daf)
(100 – (2.0 + 12.0))
The numerators and denominators used to convert a result from one basis to another basis are provided in the table below. These are multiplied by the existing analyte result to produce the analyte result at the required basis.
| Existing basis | Desired basis | |||
|---|---|---|---|---|
| As received | Air Dried | Dry | Dry Ash Free | |
| As received | 100 – M(ad) 100 – M(ar) |
100 100 – M(ar) |
100 100–(M(ar)+A(ar)) |
|
| Air Dried | 100 – M(ar) 100 – M(ad) |
100 100 – M(ad) |
100 100–(M(ad)+A(ad)) |
|
| Dry | 100 –M(ar) 100 |
100 – M(ad) 100 |
100 100–A(d) |
|
| Dry Ash Free | 100-(M(ar)+A(ar)) 100 |
100-(M(ad)+A(ad)) 100 |
100 – A(d) 100 |
|
For information on how to determine in-situ moisture, refer to Moisture in Coal.
MORE INFORMATION